8C1F642113000504 · X

MACHINESAVER / Machine 01 (GW-01) · sensor attached · replace sensor · analysis runs

Priority

low (score 6.06, higher is worse), calculated 2026-10-06 02:34:20+0000 by analysis 136b07e7a68e02d79cae560c027706f4.

LevelScoreCalculatedAnalysis
low 6.06 2026-10-06 02:34:20+0000 136b07e7a68e02d79cae560c027706f4
low 6.06 2026-09-13 23:47:36+0000 fedbba3b2278b93970a331ea8ae89573
medium 8.31 2026-09-08 08:25:24+0000 98930e87cf906734be7bce7d367aae6e

Latest KPI values (GET /mpoints-streams/{id}/kpi)

78 measurements; latest 2026-09-07 23:35.

KPILatest valuePoints in trend
rms0.1070834541358464378
velocity_rms_10_1000hz0.671319061030499778
velocity_rms_2_1000hz0.703543144545505678
velocity_rms_2_max0.705210023752703678
velocity_rms_10_max0.673065749438479678
peak0.5284370117187578
peak2peak0.862000000000000178
crest_factor4.93481477585111478
kurtosis3.124748960570969778
envelope_rms0.0210122837105509378
envelope_peak_score0.001771435043051683678

Diagnostic findings (GET /sva/136b07e7a68e02d79cae560c027706f4/symptoms and /changes/active)

No symptoms reported by the latest analysis.

Active changeTypeAt
Low FrequencylowFrequencyWarning2026-09-07 22:03
Jump in Acceleration RMS (scalar)jumpInAccRmsScalar2026-09-07 22:03
High FrequencyhighFrequencyWarning2026-09-07 22:02
Emerging ModeemergingMode2026-09-07 22:00

Trend scalars at this measuring point (GET /scalars/?sensor_id=…)

Scalars are keyed by sensor, not by stream — the link to this measuring point is derived: this point's streams name their active sources, the sources name their sensors, and the sensors' scalars are what you see here. The scalars page draws the whole chain.

SlotScalarLatestTrend
axis X acceleration_rms__X (rms) 0.155 g
axis Y acceleration_rms__Y (rms) 0.21 g
axis Z acceleration_rms__Z (rms) 0.074 g
axis X velocity_rms__X (velocity_rms) 1.22 inch_s
axis Y velocity_rms__Y (velocity_rms) 0.838 inch_s
axis Z velocity_rms__Z (velocity_rms) 0.66 inch_s
Sensor-levelLatestTrend
RSSI (untyped) -59 dBm
battery (battery) 100 %
temperature (temperature) 29 C

rpm: outside 600–3600 RPM an rpm scalar is required — without it, bearing analysis silently returns nothing.

Embedded analysis view

This iframe is the one thing the browser loads straight from the deployment. Its URL carries only the stream id — no credential — and this page's own Content-Security-Policy: frame-src header is what allows the frame (the deployment sets no framing restriction of its own).